Case Studies on Pure and Ultra-pure (deionised) water cooling and conditioning

Case Studies on Pure and Ultra-pure (deionised) water cooling and conditioning

gre 10

Portable DI Water Cooling for Linear Accelerator Cryogenic Module Test Stand

Client: European Spallation Source (ESS), Sweden  Cooling Power: 0.8 kW (800 W)  Temperature Range: Holding at 30°C ±0.5°C  Conductivity: ≤ 0.5 µS/cm  Dissolved Oxygen: <= 50 ppb   System Capacity: Multiple inlet/outlets; portable skid  Interesting System features: Standalone operation and […]

Portable DI Water Cooling for Linear Accelerator Cryogenic Module Test Stand Read More »

di pump skid cover shot

Particle Accelerator DI Cooling – Skid‑Mounted System

Client: CERN  Cooling Power: 140 kW  Temperature Range: 15–25°C with ±1°C tolerance  Conductivity: < 0.2 µS/cm  Dissolved Oxygen: < 50 ppb via membrane degassing  System Capacity: Skid‑mounted polishing/pumping loop with precision control and oxygen management  Interesting System features: Standalone or

Particle Accelerator DI Cooling – Skid‑Mounted System Read More »

pure water pump skid sector photo

STATCOM / HVDC Thyristor Cooling – Dual Redundant DI Systems

Client: New‑build power station (South Korea)  Cooling Power: 2 × 1300 kW (redundant) coupled pump/treatment and expansion skids paired with stainless steel air blast dry coolers  Temperature Range: Ambient -20°C to +50°C  Conductivity: < 0.1 µS/cm across converter valves 

STATCOM / HVDC Thyristor Cooling – Dual Redundant DI Systems Read More »

hi current cable aging rig

Thermally‑Cycled DI Water System for High‑Current Cable Ageing

Client: Alstom (for two UK high‑voltage cable manufacturers)  Cooling Power: 66 kW  Temperature Range: +10°C to +85°C with ±0.1 K tolerance  Conductivity: DI quality maintained via mixed‑bed polishing resin (≤1 µS/cm typical; lower when required)  System Capacity: Twin DI cooling

Thermally‑Cycled DI Water System for High‑Current Cable Ageing Read More »

uk grid di active fault decoupler

Active Fault De‑coupler (AFD) – Outdoor Pure‑Water Cooling

Client: National Grid (UK)  Cooling Power: 240 kW  Temperature Range: −25°C to +35°C ambient operation  Conductivity: < 1.0 µS/cm  Dissolved Oxygen: Low ppb design basis to minimise corrosion  System Components: Two pure‑water systems with run/standby pumps and auto

Active Fault De‑coupler (AFD) – Outdoor Pure‑Water Cooling Read More »

gre logo white transparent 1024x372
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.